Highlights
-
PCCC objects for Rockwell
Automation networks
supported
-
ProCOM provides a virtual
serial port for multiple DF1
and EtherNet/IP device
communication
-
8 simultaneous EtherNet/IP
clients with up to 16
simultaneous requests per
client
-
Serial redirector function
provided
-
Embedded EtherNet/IP and DF1
protocol analyzer
-
Redundant dual DC power
inputs
-
Built-in Ethernet cascading
for easy wiring
|
 |
|
|
•
Ethernet Interface |
|
Number of Ports |
2 (2 IPs) |
|
Speed |
10/100 Mbps, Auto MDI/MDIX |
|
Connector |
8-pin RJ45 |
|
Magnetic Isolation Protection |
1.5 KV built-in |
|
• Serial
Interface |
|
Number of Ports |
EIP3170/3170I: 1
EIP3270/3270I: 2 |
|
Serial Standards |
RS-232/422, software selectable |
|
Connectors |
EIP3170/3170I: DB9 male for RS-232, terminal
block for RS-422
EIP3270/3270I: DB9 male x 2 |
|
ESD Protection |
15 KV for all signals |
|
• Serial
Communication Parameters |
|
Data Bits |
8 |
|
Stop Bits |
1, 2 |
|
Parity |
None, Even, Odd |
|
Flow Control |
RTS/CTS, DTR/DSR (RS-232 only) |
|
Baudrate |
1200 bps to 921.6 Kbps |
|
• Serial
Signals |
|
RS-232 |
TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND |
|
RS-422 |
Tx+, Tx-, Rx+, Rx-, GND |
|
Ethernet Protocol |
CIP (PCCC) on EtherNet/IP |
|
Serial Protocol |
DF1 Full-duplex |
|
•
Software |
|
Driver Support |
Windows Real COM Drivers: Windows 2000, Windows
XP/2003/Vista/200/8/7 x86/x64 |
|
•
Physical Characteristics |
|
Housing |
Plastic |
|
Weight |
MGate EIP3170: 360 g
MGate EIP3270: 380 g |
|
Dimensions |
Without ears: 29 x 89.2 x 118.5 mm (1.14 x 3.51
x 4.67 in)
With ears extended: 29 x 89.2 x 124.5 mm (1.14 x
3.51 x 4.90 in) |
|
•
Environmental Limits |
|
Operating Temperature |
Standard Models: 0 to 55°C (32 to 131°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
|
Storage Temperature |
-40 to 85°C (-40 to 185°F) |
|
Ambient Relative Humidity |
5 to 95% (non-condensing) |
|
• Power
Requirements |
|
Input Voltage |
12 to 48 VDC |
|
Power Connector |
Terminal block |
|
Power Consumption |
MGate M3170: 435 mA (max.)
MGate M3170I: 555 mA (max.)
MGate M3270: 435 mA (max.)
MGate M3270I: 510 mA (max.) |
|
•
Standards and Certifications |
|
Safety |
UL 508, EN 60950-1 |
|
Hazardous Location |
UL/cUL Class I Division 2 Groups A/B/C/D,
ATEX Zone 2 |
|
EMC |
CE, FCC |
|
EMI |
EN 55022 Class A, FCC Part 15 Subpart B Class A |
|
EMS |
EN 55024,
EN 61000-4-2 (ESD) Level 3,
EN 61000-4-3 (RS) Level 3,
EN 61000-4-4 (EFT) Level 4,
EN 61000-4-5 (Surge) Level 3,
EN 61000-4-6 (CS) Level 3,
EN 61000-4-8,
EN 61000-4-11, |
|
Shock |
IEC 60068-2-27 |
|
Freefall |
IEC 60068-2-23 |
|
Vibration |
IEC 60068-2-6 |
|
•
Reliability |
|
MTBF (mean time between failures) |
MGate EIP3170: 210,794 hrs
MGate EIP3270: 125,234 hrs |
Modelos
|
|